At PS-01 · model truth
Local control continues
Demonstrations / Controls engineering
Explore communications loss, sensor faults and controlled recovery. Run the sandbox or work through four guided decisions.
Interactive teaching model / PS-01
Try: press Play → disconnect WAN → increase demand → try a supervisory command → restore WAN → confirm checks → approve recovery.
· Model step ·
Local control continues
Fresh telemetry
Tank level is a separate illustrative storage variable, not the pressure reading below. In/out values are model units per step. Play advances two model steps per second; Pause freezes the teaching model. Advance one step remains available when paused. This playback speed is not a real plant timescale. At 0% or 100% the model is clipped, not physically validated. Real pump curves, tank hydraulics and protective controls are outside this example.
Local automatic feedback control active. Target: . Demand: .
Last received sample freezes during WAN loss. It is not current plant state.
Paused · use Play or advance one step
Target change toggles 50 ↔ 60 only when authority is enabled. Rejected commands are discarded, never queued. Restoring the link restores telemetry, not supervisory authority. Confirming checks is an educational interaction, not real equipment verification. No external connections or saved results.
Teaching fallback: PT-01 bad quality suspends feedback and holds the last modeled pump output until repair, checks and approval. The process can still change under demand. This arbitrary demonstration is not a safe state or an instruction to hold a real pump. Actual fallback, escalation limits and stop conditions require a site hazard review and approved procedure.
Tank and flow drawings show teaching-model truth, with separate illustrative telemetry. PT-01 measures pressure, not tank level; a pressure sensor fault does not freeze unrelated telemetry. No independent physical sensors or real protection are implemented here.
Learn by deciding / 5–10 minutes
Four guided scenarios compare communications loss, sensor failure, both faults and recovery. Each loads a paused state into the model above. Manual simulation controls are locked during the exercise so the question matches the state. Starting or restarting replaces your sandbox state. Answers are held in memory for your end-of-exercise review; nothing is saved persistently or sent.
The snapshot exposes local model truth for learning. SCADA cannot know new local faults during a communications outage.
Use approved site procedures and responsible operations/engineering authority in real facilities. No generic answer here authorizes a physical change or establishes a safe operating state.
This dimensionless model illustrates failure and recovery concepts. It does not validate a water utility architecture or any plant acceptance test. No live utility is represented. See the companion article for the design, sources and unexecuted acceptance plans.